E- BUS ,4-core FRNC and 4-pair PVC
Application
The E-bus cable is used for the transmission of bus signals for intelligent systems in buildings. The cables ensure perfect communication in accordance with EIB regulations (European installation bus). They can be installed over, in, or below the plaster, in pipes and pipe ducts, in dry, moist, and wet areas, as well as outside, provided they are protected against direct exposure to the sun. Wiring together with high-power supply cables is possible without limitation. The EIB bus can be used to control lighting, blinds, heating, ventilation, indicator boards, etc.
|
|
Type |
2 Pairs |
2 Pairs |
Construction du câble |
2x2x0.8 mm |
2x2x0.8 mm |
Inner Conductor Diameter: |
Copper, bare |
Copper, bare |
Chef d'orchestre d'isolation: |
PVC |
PVC |
Couleurs d'orchestre: |
white, yellow, red, black |
white, yellow, red, black |
Echouage Element: |
Star quad |
Star quad |
Shielding 1: |
Polyester foil over stranded bundle |
Polyester foil over stranded bundle |
Shielding 2: |
- |
- |
Total Shielding: |
Polyester foil, aluminum-lined |
Polyester foil, aluminum-lined |
Drain Wire: |
yes |
yes |
Outer Jacket Material: |
PVC |
PVC |
Outer Cable Diameter: |
6.6 mm ± 0.3 mm |
6.6 mm ± 0.3 mm |
Outer Jacket Color: |
Blue Lilac similar to RAL 4005 |
Green similar to RAL 6010 |
|
|
Caractéristiques électriques |
|
Impédance caractéristique: |
100 Ohm |
100 Ohm |
Chef d'orchestre de résistance: |
73.2 Ohm/km max. |
73.2 Ohm/km max. |
Tension nominale: |
0.10 GOhm x km min. |
0.10 GOhm x km min. |
Tension de test: |
100.0 nF/km nom. |
100.0 nF/km nom. |
|
Poids: |
approximately 54.0 kg/km |
approximately 54.0 kg/km |
Min. Bending Radius (Laying): |
95.0 mm |
95.0 mm |
Operating Temp.Range, min.: |
- 30 °C |
- 30 °C |
Operating Temp.Range, max.: |
+70 °C |
+70 °C |
Caloric Load, approx. value: |
0.90 MJ/m |
0.90 MJ/m |
Copper Value: |
25.0 kg/km |
25.0 kg/km |
|
Applicable Standards: |
EIB Standard |
EIB Standard |
|
|
|
|
|
|
|